Creche Inspection Reports

Regulation 26 in Dublin

Fire safety measures: 94 non-compliance(s) in the latest reports we read.

An inspection records what inspectors saw on one day; services respond with corrective actions — how to read this.

23 June 2026

School Kids Aloud, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (b) The maintenance of smoke alarms was completed 25 June 2026 and the record was made available and submitted to the agency 25 June 2026. The service has renewed their contract, and maintenance will be completed annually

18 June 2026

Purple Turtle Montessori, Malahide · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider has confir med that a contract is now in place for maintenance of the smoke detection system. Records of smoke alarm maintenance will be available going forward

13 May 2026

St. Nicholas Montessori Merrion, Dublin 4 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (4) The registered provider stated that notices are now displayed in all rooms. A review of the fire safety policy with staff will take place at the beginning of each year. A staff member will be appointed to ensure all signage is in good condition and clearly visible, replacing any faded signs, and ensuring that any changes are notified to substitute staff, and staff will receive training on the service’s fire safety policies

7 May 2026

St. Michael's College Pre-School, Dublin 4 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider stated that fire drills occur monthly and that going forward fire drills will be recorded and on display

5 May 2026

St. Nicholas Montessori School Blackrock, Blackrock · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(a) The registered provider stated that the pastoral centre carries out fire drills a number of times a year and the preschool take part in these drills. Going forward we will carry out and record our own fire drills on a monthly basis, in addition to joining the drills organised by the pastoral centre

29 April 2026

Our World Montessori Ltd., Blackrock · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider stated that the latest maintenance certificates of smoke alarms and fire extinguishers were obtained. The maintenance checks were completed within the previous twelve months, but the certificates were not available for inspection on the day. A check for valid certificates will be carried out monthly to ensure that certificates are on site when needed

28 April 2026

Bright Futures Creche, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(b) The fire company was contacted, and the service of the firefighting equipment was carried out immediately after the inspection. Preventive Action (1)(b) Management spoke with the fire company about continuing up-to-date services

15 April 2026

The Nest/Kinsealy Childcare Ltd, Kinsealy · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The service smoke alarm report submitted. Preventive Action (b) On a yearly basis, the Manager and Assistant Manager will check and verify that smoke alarm reports are available on site for inspections and for record-keeping purposes

1 April 2026

Happy Phases Pre-School, Dublin 12 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The person in charge has stated that regular fire drills have resumed and a reminder has been set on the calendar for a monthly drill

26 March 2026

Cool Kidz Creche, Dublin 16 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (4) The person in charge has drawn up map of the class with instructions on how to exit the service in the event of a fire. This is on display on the wall in the care room. The map with the procedure to be followed in the event of a fire will remain on the wall in a visible area

23 March 2026

Maywood Montessori, Dublin 5 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (b) Firefighting equipment and smoke alarms have been serviced. A contractual arrangement has been established to ensure ongoing servicing of equipment

19 March 2026

Eco Kidz Park Avenue, Sandymount · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The fire extinguishers have been serviced and a fire safety compliance checklist has been introduced by the Railway Union Management to ensure annual servicing certificates are requested, received and filed in advance of expiry date. Responsibility for monitoring and updating fire safety records has been assigned to the designated fire safety officer to ensure ongoing compliance is met in line with the Fire Safety Policy

19 March 2026

St. Michael's Preschool & Afterschool Service, Dublin 10 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The person in charge has set up a system to remind them when the fire certificates need to be renewed

11 March 2026

Willow Montessori School, Dublin 18 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider has stated that the smoke detectors have now been serviced. The registered provider has also stated that they have now taken ownership of the fire safety maintenance to avoid repeat non-compliance

10 March 2026

Doreen's Preschool Montessori, Dublin 7 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (4) There is a notice of procedures to be followed displayed on the wall beside the door in the playroom. It is above the fire extinguishers. It is also on display in Montessori room

9 March 2026

An Cosán Early Years - Colaiste Eanna, Dublin 7 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • In response to the non-compliance the service has stated that they have engaged with a company to undertake regular inspections and complete an inspection to ensure that all smoke alarms and emergency lighting are compliant and this carried out 21/04/2026. The date of next service due is scheduled

12 February 2026

Balcunnin Learn'Play Preschool, Skerries · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The smoke alarms were tested and checked and all working satisfactorily, and this was carried out on 11th March 2026 and a copy of invoice sent to inspectorate by email. A new fire extinguisher has been bought, and the invoice has been forwarded to inspectorate. Preventive Action (b) It has been arranged for the service to be done yearly

12 February 2026

Castlefield Montessori School, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Smoke alarms and emergency lighting were checked on 18 February 2026. The registered provider has stated the smoke alarms will be checked on a regular basis

12 February 2026

Minerva Montessori, Dublin 6 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider has stated that two fire drills have been carried out since the inspection. A member of staff has now been assigned the responsibility for carrying out and documenting fire drills

8 January 2026

Little Scholars Montessori & Childcare Limited, Lusk · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The registered provider organised for the Fire Company to go out to the service and inspect all fire extinguishers and smoke detectors on the premises. Preventive Action (b) A reminder has been set in HR documents to arrange inspections every year going forward

19 December 2025

Ready Steady Play, Dublin 22 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The service obtained the annual fire alarms serving report from the shopping centre management. The service have put the next date due for the fire alarms servicing in their diary and will ask the shopping centre management on an annual basis that they give a copy of the servicing records for their records, so they are available always for inspection by the Fire Safety Officer or Tusla

11 December 2025

Little Scholars Montessori and Childcare Limited, Lusk · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) In response the service organised for the fire extinguishers and smoke detectors in the service to be serviced. A reminder will be sent to us when the new maintenance inspection needs to be done every year

1 December 2025

Naíonra Santain Teoranta, Dublin 24 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • We have completed a change of circumstances form to Tusla which has been accepted. We will ensure any further change of circumstances are applied for

1 December 2025

Naíonra Santain Teoranta, Dublin 24 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (4) There was notice of the procedures to be followed in the event of a fire on the door, but it was written in Irish and was overlooked. We have now printed an English version to accompany it in case of visitors to the service

20 November 2025

Community After Schools Project (SM), Dublin 1 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The RP obtained the fire maintenance certificate from the buildings facilities manager which shows a dated inspection of the equipment on 29 August 2025. The service has requested their own copy of the smoke alarm and fire equipment maintenance report so that it is available and onsite for future inspections

12 November 2025

Green Gables Montessori/Playschool, Portmarnock · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) Fire maintenance company attended Green Gables on the 14th of January to service fire equipment. Preventive Action (b) Fire maintenance company will attend annually to service fire equipment

11 November 2025

Sticky Fingers, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(a) The fire drill document has been updated. Management will ensure the fire drill record has the updated fields. (4) The procedure to follow in the event of an evacuation has been displayed on the wall. In future the procedure to follow in case of evacuation will always be displayed

6 November 2025

St Brigid's Montessori School, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The Fire Safety Officer returned to rectify this matter. Signatures were in the fire safety book. The Fire Safety Officer signed again on the day. Preventive Action (b) The fire safety book has pages marked for future inspection. The Fire Officer is due to return to service at the beginning of next years’ school term. This is also marked in diary and checklist

5 November 2025

Deerpark Montessori School, Howth · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(a) Following the Tusla inspection, a fire drill was carried out with the children. This drill was fully documented, and the record was added to our daily logbook using the updated fire safety template. At present, they have completed and recorded two fire drills, one in November and one in December. (b) Manager requested smoke detector inspection certificate from landlord. Documentation not yet received due to delays caused by staff illness and ongoing alarm system upgrades. Preventive Action (1)(a) The service has implemented a monthly fire drill schedule, to be conducted during the first week of each month. All fire drills will be recorded in the daily logbook using the fire safety template, and documentation will be kept on file for inspection to ensure compliance with Regulations. (b) Certificate will be forwarded as soon as received. Annual alarm checks will be requested and kept on file going forward

28 October 2025

Lakelands Childcare, Stillorgan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (a) A fire drill was carried out in November and drills will be conducted monthly going forward. Fire drills have been added to the managers task list to ensure they are planned and carried out consistently

22 October 2025

Kilmore West Community Playgroup, Dublin 5 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective & Preventive Action (1)(b) The registered provider submitted the maintenance record for the 1 December 2025 for the fire alarm and will ensure annual servicing. Summary Comment The actions and evidence submitted by the new registered provider, in their corrective and preventive action plan, has addressed the non-compliance

14 October 2025

The Kids Den ASD Services Limited, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(a) A fire drill was carried out on the 15 October. The drill was recorded using the updated fire drill log. Fire safety documentation has been reviewed, and all records are now stored together in the fire safety folder on site. Staff received refresher training on fire drill procedures and documentation requirements. Preventive action To prevent this issue reoccurring , a fire drill schedule has been created to ensure drills occur at least every four weeks. The fire drill log has been updated and will be checked monthly by management. A calendar reminder has been added to ensure fire drills cannot be missed. All fire safety documents will be kept onsite in a clearly labelled fire safety folder

3 October 2025

Child's Play Creche, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1) (b) Request for records. As the registered provider rents part of the community building, the smoke alarm maintenance records have been formally requested from the committee. The registered provider is currently awaiting their provision. In the meantime, the service has conducted a full internal audit of all smoke alarms within the area the service occupies. All alarms have been visually inspected, tested where possible, and are operational with no faults detected on the control panel. Once the maintenance records are received, the se will be added to service’s safety log , and they will maintain a complete record of all smoke alarm checks, tests, and maintenance activities to ensure compliance with Regulation 26 (1) (b). Preventive Action (1) (b) Going forward, regular contact will be maintained with the management committee to ensure that all smoke alarm maintenance records are up-to-date and provided promptly. Summary Comment The inspector has reviewed the actions and evidence submitted. It is acknowledged that the registered provider has taken action in relation to the smoke alarm maintenance records. However, as these records have not yet been submitted, the non-compliance under Regulation 26 (1) (b) in relation to the smoke alarm still remains outstanding. It is the responsibility of the registered provider to furnish the smoke alarm maintenance certificate to the inspectorate when received

2 October 2025

Drumcondra Montessori School, Dublin 9 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (b) The firefighting equipment was checked and certified after the inspection and yearly checks have been scheduled. The registered provider stated that a suitable smoke detection system is in place and regular checks are carried out

1 October 2025

Prospect Montessori, Dublin 9 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider arranged for a new contractor to ensure the maintenance of the smoke alarms, and an up-to-date maintenance certificate was submitted the day after the inspection

29 September 2025

Play Days Pre-school, Dublin 18 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) New company sought to check fire extinguishers. The fire extinguisher have been checked and a new cert have been issued

24 September 2025

Bremore Castle Montessori, Balbriggan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) An appointment was made straight away. Fire extinguishers were serviced. Registered provider is still waiting on smoke alarms appointment. Preventive Action (b) Check maintenance records for smoke alarms & fire extinguishers records

24 September 2025

Spraoi Montessori, Lucan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (a) A fire drill was carried out with children attending the morning and afternoon sessions. Children were given clear instruction and evacuated the premises promptly and safely. Going forward fire drills will take place on a monthly basis and a record for each drill will be maintained. (b) Fire extinguishers and smoke alarms were serviced. The registered provider has put a system in place to ensure annual servicing takes place on all fire equipment

18 September 2025

Casa dei Bambini Montessori, Dublin 3 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • A visual notice of the procedures to be followed in the event of a fire has been displayed around the service

15 September 2025

Hope Montessori Autism Care Centre, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) In response the registered provider has stated that the equipment was serviced a week before the inspection. The certificate was emailed to the inspector as soon as received. Service will continue to ensure that all firefighting equipment is serviced as and when due, with up-to-date certificates provided and kept on file

15 September 2025

Early years service TU2015DY156, Dublin 9 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) The smoke alarms were serviced on the 26 September 2025. The registered provider has reminders now in place to ensure to get the smoke alarms serviced in August each year

9 September 2025

Youth Horizons Creche, Dublin 24 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Click or tap here to enter text

1 September 2025

Kinsealy Woods Creche and Montessori, Kinsealy · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) Since inspection a new contractor has been acquired by the service to carry out maintenance on the fire alarm and smoke alarms. Preventive Action (b) Maintenance will be conducted on a quarterly basis, managers will ensure that this is monitored, and records are kept of any maintenance visits

13 August 2025

Kidz Zone, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (4) In response the registered provider has stated that clear instructions are now in place on the walls of where fire safety point is and clear staff roles and responsibilities in the event of a fire/drill. Management will complete a weekly morning check to ensure that fire safety procedures are clearly displayed in all rooms

7 August 2025

Ups A Daisy Childcare, Dublin 12 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider submitted the following response: Corrective and Preventive Action The fire drill procedures are now displayed on the back of every classroom door. These procedures will be practiced each month

14 July 2025

Wee Tots Creche and Pre School, Dublin 8 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (b) The service submitted evidence that the fire alarm system was maintained on the 24 July 2025. The service will ensure this check is conducted annually. (4) Notices are now displayed in the Butterfly and Toddler room 2 and the service report they will complete regular checks to prevent a recurrence

1 July 2025

Dara's Creche, Dublin 24 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The firefighting equipment has now been serviced, and the maintenance was carried out on the fire alarm and detection system. The records are hanging in the hall and on view

19 June 2025

Lakelands Preschool, Dun Laoghaire · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered providers submitted evidence of quarterly servicing of the fire detection systems and annual servicing of firefighting equipment. The registered providers will ensure that documents are filed for access for inspection by authorised persons

19 June 2025

Little Apples Ltd, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) The registered provider submitted a maintenance certificate for the fire extinguishers for June 2025. The registered provider and maintenance company have a system in place as a reminder of maintenance requirements

18 June 2025

Sunshine Creche & Montessori Ltd, Dublin 9 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (a) A fire drill was conducted following the inspection on 18 June 2025. Responsibility for monthly fire drills have been allocated to a staff member

18 June 2025

The Village Montessori, Malahide · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(a) Their fire drills record book has been updated. (b) Registered provider has contacted the Yacht Club to send them the details required and to send them the most recent certificate. Preventive Action (1)(a) Monthly reminders are put in place to record monthly fire drill. (b) Registered provider will be requesting these details from the yacht club annually

17 June 2025

Little Treasures Preschool Playgroup, Dublin 12 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • A new fire and smoke maintenance book has been purchased for the setting which keeps track of the maintenance checks done. The new book will be kept in the room and up to date

10 June 2025

Child's Play, Dublin 8 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The firefighting equipment was serviced and certified in August 2025. An appointment to have the fire alarm and smoke alarms serviced was confirmed for 25th of August 2025 and rescheduled to 28th of October 2025. Preventive Action (b) Management have made note of the next required service dates and have reminders set to arrange the service before that time

4 June 2025

Really Cool Afterschool & Montessori School, Balbriggan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(b) Certificate is now displayed on the wall. Preventive Action (1)(b) Regular checks

21 May 2025

Lámha Beag, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(a) The registered provider submitted a copy of fire drills which had been completed since the inspection. They stated that a spreadsheet showing date last drills took place are now in the service for easy monitoring. (1)(b) The maintenance records for the fire alarm system and the fire extinguishers were submitted as the registered provider had to source a new contractor. This company will keep a log of when the next service is due and will call out before expiry date

13 May 2025

The Nest Ranelagh, Dublin 6 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (b) A maintenance check was carried out on all smoke alarms and will be checked quarterly going forward

9 May 2025

Absolute Angels, Malahide · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action 1(b) Firefighting equipment and smoke alarms have been serviced and an up to date record is available and included in the files. Preventive Action 1(b) The service have scheduled a yearly service of firefighting equipment with a fire protection company

8 May 2025

Daisy Days Montessori, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (b) The smoke alarm system was serviced the day after the inspection. Management have arranged for maintenance checks to be carried out by an external contractor on a 6-monthly basis

29 April 2025

Magnolia Montessori, Dublin 6W · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The service of the smoke alarm has been completed, the registered provider and the building management will make a note of the servicing dates and contact the fire company in advance of each service to book it in

15 April 2025

Little Stars Childcare, Dublin 11 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (a) A fire drill was completed on the 19 May 2025; a staff member has been assigned with recording monthly fire drills. (4) Documentation of fire procedure map on wall outlining exits. All fire extinguishers have been updated plus fire alarms updated, make sure they are checked regularly

10 April 2025

Cocoon Childcare- Artane, Dublin 5 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (b) A full service was carried out on the fire system the following day. The management team have scheduled the next visit for 6 months’ time with the company and set reminders for subsequent visits which have been shared with the operations manager

4 April 2025

Parkside Early Learning, Dublin 7 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The registered provider contacted the building management in relation to the smoke alarm certificate. The fire maintenance company was closed and unable to provide smoke alarm certificate. The registered provider reported that the service deems fire safety extremely important. The service received a quotation from a new fire safety company. Fire alarm testing was carried out on the 11th of June with a smoke alarm certificate issued on the 11th of June 2025. Preventive Action (b) The registered provider has requested a direct copy of fire maintenance be sent to them, so they know when maintenance is due

4 April 2025

Stepping Stones, Garristown · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) The maintenance of the fire extinguisher has been completed. Preventive Action (b) Registered provider has asked Northeast Fire to complete a yearly maintenance check, every March going forward

27 March 2025

Naìonra Uì Hearcàin, Dublin 11 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(a) A new procedure has been implemented to ensure fire drills are conducted and recorded on a monthly basis, a designated member of staff member has been assigned this task, going forward on a new school term a designated person will be nominated to oversee this task

24 February 2025

Springfield Montessori School, Dublin 18 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The service will ensure monthly fire drills take place and are recorded and stored appropriately to ensure they are available for inspection

4 December 2024

Enchanted Abbey Montessori School, Lucan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) inspection carried out on fire extinguishing equipment. Taken note in diary of date for next inspection

3 December 2024

Acorns Montessori, Rush · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider stated the following corrective actions and preventive actions have been undertaken: Corrective Action & Preventive Action The registered provider had had the servicing completed on time but did not have the document available when the inspector was here. The registered provider will ensure that all documents for proof of servicing are immediately requested and put on file

3 December 2024

Tiny Tots-Preschool, Lusk · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(a) registered will keep a record of fire drills on display and done every month. (b) register provider has arrange for the fire extinguisher and fire alarm to be serviced in January and she will send on copy of certificate. Preventive Action (1)(a) Registered Provider will keep the register on display where it can be seen. (b) Registered provider will ask the company to put her in for a yearly check on the fire extinguisher/fire alarm

19 November 2024

An Cosán Early Years Whitehall, Dublin 9 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action The maintenance of fire extinguishers has been completed. All extinguishers have been serviced, and the maintenance receipt and invoice have been provided. A certificate is still pending and will be forwarded once received. Preventive Action The service has engaged a company to maintain the fire extinguishers and maintenance will be conducted on a yearly basis. Fire Certificate has been received for maintenance

19 November 2024

The Orchard Playschool, Dublin 5 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (b) Our fire extinguishers were serviced on the 27th of November 2024, the certificate is now displayed in the school. We have set a reminder in our calendar for fire equipment service expiry

29 October 2024

The Kilns Creche & Montessori LTD, Portmarnock · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(b) Manager was speaking to our management company, they are waiting for an engineer to complete the smoke alarm tests. Preventive Action (1)(b) Manager will keep in contact with the management company to ensure these safety measures are carried out. Their other fire safety equipment has been certified

21 October 2024

AVS Montessori t/a Daisy Montessori, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) The fire extinguishers were serviced on 20 November 2024; the registered provider will check the fire extinguishers regularly

16 October 2024

Teacher Pats Playschool, Dublin 12 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider submitted the following response: Corrective and Preventive Action The service informed the fire and safety company of the delay in servicing, this was rectified with an inspection the following day. To prevent this non-compliance, the service are booked in with the fire and safety company for next year

11 October 2024

Ros-Eo Community Preschool, Rush · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider stated the following corrective actions and preventive actions have been carried out: Corrective Action (4) This was discussed with staff to ensure notices are not covered for health and safety reasons. All new procedure notices were applied by a fire safety company and a new evacuation procedure notice fixed to wall. Preventive Action (4) More staff awareness to ensure all notices are visible

23 September 2024

Rose Cottage, Dublin 11 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action The fire extinguisher was serviced. Preventive Action The service will check the yearly renewal date

18 September 2024

Eco Kidz Sportsco, Dublin 4 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action Management displayed a new evacuation fire procedure on the board, on the day of the inspection we had a child-friendly fire procedure evacuation displayed on the board. Preventive Action Management will make sure that we have both fire evacuation procedures displayed on the board in the hall

16 September 2024

Hansel & Gretel Playschool, Lucan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Company that deals with the smoke alarms was immediately contacted, and the inspection was carried out within a few days, and cert issued to inspector on 24/09/2024. Company have been instructed / engaged to carry out annual inspections, by the owners of the building

17 June 2024

New Horizons Montessori School, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action & Preventive Action (b) An appointment has been arranged with the Fire Safety Officer to complete the maintenance work required. A copy of the new certificate will be submitted as soon as this visit has been completed. Manager has set up an annual reminder from the date of this visit to ensure that the annual review of their fire equipment is completed at the appropriate time

13 June 2024

Playdays Playschool, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) None submitted

6 June 2024

Lovable Me Preschool, Dublin 13 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(a) Staff advised fire drill records must be kept accurate. As soon as fire drill is completed, records must be updated on the same day. Management will complete weekly checks and schedule fire drill once a month for both classes

6 June 2024

St. Brigid's Playgroup, Dublin 5 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (b) We contacted the club immediately asking for relevant smoke alarm maintenance certificate. They could not find the most up to date certificate. They organised for a company to do these service checks immediately and this was completed 19/06/24. We spoke with the fire company; they recommended that smoke alarm and fire system is checked every 6-12 months, and they usually contact the Football club when checks are due. We have asked them to contact us too so we can ensure that the football club is up to date with all the fire safety requirements

17 May 2024

Little Bambinos Childcare, Dublin 12 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Servicing of the smoke detection and alarm system took place on the 17 June 2024 and regular servicing of the system has been scheduled going forward

16 May 2024

Cheeky Monkeys Playschool, Malahide · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The registered provider stated the following corrective actions and preventive actions have been carried out: Corrective Action (1)(b) A trained person service d the fire extinguisher on 23/05/2024 and the maintenance certificate was immediately forwarded to the Inspectorate. Preventive Action (1)(b) The fire extinguishers will be serviced annually

10 May 2024

Lollipops Centre Limited, Dublin 15 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The service submitted evidence that the smoke alarm system was maintained on the 23 May 2024. The service commit to maintaining a record of the maintenance of the smoke alarm system

9 May 2024

Mary’s House Tallaght, Dublin 24 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • The service has entered a contract to have maintenance done on the smoke alarm system. The contract is to have the smoke alarm system inspected every quarter

1 May 2024

Circle of Friends, Balbriggan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) Two new fire extinguishers were purchased, and the receipt is displayed to show date of purchase. Preventive Action (b) The fire extinguishers will be serviced yearly, and a record kept, alternatively replace with new extinguishers, and display receipt to display date of purchase

1 May 2024

Lorraine's Montessori School, Balbriggan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (b) Two new fire extinguishers are in place with receipt of date of purchase. Preventive Action (b) Fire extinguishers will be serviced yearly

23 April 2024

Little Feat, Dublin 14 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • A copy of fire evacuation procedures are now in place in each room/area. Fire Drill officer will check to ensure the fire evacuation procedures are still available in each room prior to carrying out monthly fire drill

11 April 2024

Creative Days Preschool, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • Corrective Action (1)(a) Fire Drills will be conducted monthly to familiarise the staff and children with fire evacuation routine. (b) A record was not available of the number, type, and maintenance of smoke alarms in the premises on the day of inspection. All fire equipment including the services fire alarms were serviced on 3/10/23 and are serviced annually. On the day of the inspection the staff had available a Certificate which they believed was representative of the fire equipment service. On closer inspection we now realise that the smoke alarms service was omitted on this Certificate. Preventive Action (1)(a) All staff have reviewed our Health & Safety Policy which includes Fire Safety. A reminder alarm has been set on their school phone to remind staff to conduct fire drills monthly. (b) Manager has now printed out the relevant document of receipt for fire alarm service and will ensure going forward that both documents are printed annually,

10 April 2024

Sandymount Green Montessori, Dublin 4 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) Firefighting equipment was serviced after the inspection. The manager was advised to check that the Firefighting equipment is serviced on an annual basis as required

6 March 2024

Bo-Peep Crèche & Montessori, Swords · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (b) Registered provider has the book handy and available. the book is signed off quarterly by the fire maintenance company and is kept on the premises. Preventive Action (b) The book couldn’t be placed on the day of inspection but has now been allocated a specific spot to be kept in at all times

10 January 2024

Eden Early Learning Centre, Dublin 8 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (2)(b) Smoke alarms have been maintained and certified. Arrangements have been set up with direct power and fire services to complete a bi-annual maintenance and check

10 January 2024

Really Cool Afterschool & Montessori School Ltd, Balbriggan · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1)(b) The record was on the wall on the day of inspection , just wasn’t seen. Photo was provided, no action required, the maintenance is regular and ongoing

14 September 2023

Our World Montessori, Dublin 5 · Regulation 26 — Fire safety measures

Provider's corrective action:
  • (1) (a) Fire drills commence at the end of each month and had not yet taken place for September. Fire drills take place at the end of each month. (b) Fire Extinguisher and smoke alarm have been serviced and up to date cert obtained. Renewal service date logged and noted for service of fire extinguisher and smoke alarm. (2)(c) & (3) File division created to maintain fire drills log for five years

Regulation 26 in other counties